检查母线及引下线连接是否良好,母线接头处有无变形,有无放电变黑痕迹,检查母线上的绝缘有无松动和损坏。检查电缆头、接线桩头是否牢固可靠,检查接地线有无锈蚀,接线桩头是否紧固,确保接头连接紧密。。 用手柄把总空气从配电柜中摇出,检查主触点是否有烧溶痕迹,检查灭弧罩是否烧黑和损坏,紧固各接线螺丝、清洁柜内灰尘,试验机械的合闸、分闸情况把各分开关柜从抽屉柜中取出,紧固各接线端子。检查电流互感器、电流表、电度表的安装和接线,检查手柄操作机构的灵活可靠性,紧固空气开关进出线,清洁开关柜内和配电柜后面引出线处的灰尘
Check whether the connection between the bus bar and the lead line is good, whether there is any deformation at the bus joint, whether there are any traces of discharge and blackening, and check whether the insulation on the bus bar is loose or damaged. Check whether the cable head and connection pile head are firm and reliable, check whether the grounding wire is corroded, whether the connection pile head is fastened, and ensure the connection of the joint tightly. Handle the total air from the power distribution cabinet shake out, check whether there is the main contact fused traces, check whether the arc shield burned black dust and damage, fastening the connecting screws, clean cabinet, mechanical test of closing and opening of the separate closed cabinet is removed from the cabinet, fastening the terminal. Check the installation and wiring of current transformer, ammeter and watt hour meter, check the flexibility and reliability of the handle mechanism, fasten the air switch inlet and outlet, clean the dust in the switch cabinet and the rear outlet of the distribution cabinet.