配电柜接线工艺规范
配电柜接线工艺规范
Technical specification for wiring of distribution cabinet
元器件的安装
Installation of components
1、前提:所有元器件应按制造厂规定的安装条件进行安装。
1, premise: all components should be installed according to the installation conditions specified by the manufacturer.
适用条件:需要的灭弧距离,拆卸灭弧栅需要的空间等,对于手动开关的安装,必须保证开关的电弧对操作者不产生危险 。
Applicable conditions: the required arc extinguishing distance, the disassembly of the space required by the arc extinguishing grid and so on. For the installation of the manual switch, it is necessary to ensure that the arc of the switch does not pose a danger to the operator.
2、组装前首先看明图纸及技术要求。
2. First look at the drawings and technical requirements before the assembly.
3、检查产品型号、元器件型号、规格、数量等与图纸是否相符。
3, check the product type, component type, specification, quantity and so on and drawings.
4、检查元器件有无损坏 。
4. Check whether the components are damaged.
5、必须按图安装
5, it must be installed according to the diagram
6、元器件组装顺序应从板前视,由左至右,由上至下。
6, the assembly sequence of components should be viewed from the front panel, from left to right, from top to bottom.
7、同一型号产品应保证组装一致性。
7, the same type of product should ensure the consistency of assembly.
8、面板、门板上的元件中心线的高度应符合规定:
8. The height of the centerline of the panel and door panel should meet the requirements:
组装产品应符合以下条件:
The assembled products should meet the following conditions:
①操作方便。元器件在操作时,不应受到空间的防碍,不应有触及带电体的可 能。
The operation is convenient. During operation, components should not be obstruct by space and should not be touched by electrified bodies.
②维修容易。能够较方便地更换元器件及维修连线。
It's easy to repair. It can replace components and maintain connection conveniently.
③各种电气元件和装置的电气间隙、爬电距离应符合4.4 条的规定:(保证一、二次线的安装距离)
(3) the electrical clearance and creepage distance of various electrical components and devices should comply with 4.4 regulations: (to ensure the installation distance of the one or two line).
1) 组装所用紧固件及金属零部件均应有防护层,对螺钉过孔、边缘及表面的毛刺、尖锋应打磨平整后再涂敷导电膏。
1) the fasteners and metal parts used in the assembly should have protective layers, and the spines on the holes, edges and surfaces of the screws and the sharp front should be polished and then coated with the conductive paste.
2) 对于螺栓的紧固应选择适当的工具,不得破坏紧固件的防护层,并注意相应的扭距。
2) for the fastening of bolts, proper tools should be selected, the protective layer of fasteners should not be damaged, and the corresponding torque should be noted.
3) 主回路上面的元器件,一般电抗器,变压器需要接地,断路器不需要接地,下图中为电抗器接地。
3) the components on the main circuit, the general reactor and the transformer need to be grounded, and the circuit breaker does not need to be grounded.
4) 对于发热元件 (例如管形电阻、散热片等) 的安装应考虑其散热情况,安装距离应符合元件规定。额定功率为75W 及以上的管形电阻器应横装,不得垂直地面竖向安装。
4) for heating elements, such as tubular resistance, heat sink, etc., the heat dissipation should be considered, and the installation distance should comply with the component requirements. Tubular resistors with rated power of 75W and above shall be installed horizontally, and shall not be installed vertically on the ground.
5) 所有电器元件及附件,均应固定安装在支架或底板上,不得悬吊在电器及连线上。
5) all electrical components and accessories should be fixed on the bracket or the bottom plate, and shall not be hung on electrical appliances and wiring.
6) 接线面每个元件的附近有标牌,标注应与图纸相符。除元件本身附有供填写的 标志牌外,标志牌不得固定在元件本体上。
6) there are signs near each component of the wiring surface, and the marking should be consistent with the drawings. Except for the sign attached to the component itself, the sign must not be fixed on the component body.
7) 标号应完整、清晰、牢固。标号粘贴位置应明确、醒目。
7) the labeling should be complete, clear and firm. Sticker position should be clear and eye - catching.
8) 安装于面板、门板上的元件、其标号应粘贴于面板及门板背面元件下方,如下方无位置时可贴于左方,但粘贴位置尽可能一致。
8) the components installed on the panel and door board shall be attached to the underside of the panel and the back of the door panel, which can be attached to the left side if there is no position below, but the position of the sticker is as consistent as possible.
9) 保护接地连续性
9) protection of grounding continuity
保护接地连续性利用有效接线来保证。
The continuity of protection is ensured by using effective wiring.
柜内任意两个金属部件通过螺钉连接时如有绝缘层均应采用相应规格的接地垫圈并注意将垫圈齿面接触零部件表面(红圈处),或者破坏绝缘层。
When any two metal parts in the cabinet are connected through screws, the corresponding ground washer should be used,chuguo.37ix.com.cn yalvjid.89ix.comtiaojiefad.89ix.com qiufab.89ix.comtuoshuijis.89ix.comtuoshuijil.89ix.com such as the insulating layer, and the contact surface of the washer is contacted with the surface of the parts (red ring), or the insulation layer is destroyed.
门上的接地处(红圈处)要加“抓垫”,防止因为油漆的问题而接触不好,而且连接线尽量短。
The "grounding pad" should be added to the ground (red circle) on the door to prevent contact problems due to the paint problem, and the connection line is as short as possible.
10) 安装因振动易损坏的元件时,应在元件和安装板之间加装橡胶垫减震。
10) when installing components that are easily damaged due to vibration, rubber pad shall be installed between components and mounting plates to reduce vibration.
11) 对于有操作手柄的元件应将其调整到位,不得有卡阻现象。将母线、元件上预留给顾客接线用得螺栓拧紧。
11) for components with handles, they should be adjusted in place and not stuck. The busbar and components are pre reserved for customer wiring to be tightened by bolts.
二次回路布线
Two circuit wiring
1、 基本要求:
1. Basic requirements:
按图施工、连线正确。二次线的连接(包括螺栓连接、插接、焊接等)均应牢固可靠,线束应横平竖直,配置坚牢,层次分明,整齐美观。同一合同的相同元件走线方式应一致。
The construction and connection are correct according to the diagram. The connection of the two line (including bolt connection, socket, welding and so on) should be firmly and reliably, the wire harness should be horizontal and vertical, the configuration is firm, the level is clear, and the neat and beautiful. The same elements should be aligned in the same contract.
2、二次线截面积要求:
The 2 and two line intercepting area requirements:
单股导线不小于1.5㎜²
Single strand conductors are not less than 1.5
多股导线不小于1.0㎜²
Multi strand conductors are not less than 1
弱电回路不小于0.5㎜²
Weak circuit is not less than 0.5
电流回路不小于2.5㎜²
Current circuit is not less than 2.5
保护接地线不小于2.5㎜²
Protective earthing line is not less than 2.5
3、所有连接导线中间不应有接头。
3. There should be no joint in the middle of all connecting wires.
4、每个电器元件的接点最多允许接2根线。
4, the contact points of each electrical component are allowed to receive 2 wires at most.
5、每个端子的接线点一般不宜接二根导线,特殊情况时如果必须接两根导线,则连接必须可靠。
5, the wiring points of each terminal are generally not suitable for two conductors. In case of special circumstances, if two wires must be connected, the connection must be reliable.
6、二次线应远离飞弧元件,并不得防碍电器的操作。
The 6 and two times lines should be far away from the arc components and must not obstruct the operation of electrical appliances.
7、电流表与分流器的连线之间不得经过端子,其线长不得超过3米。
7. The terminals between the ammeter and the shunt shall not pass through the terminals, and the length of the wires shall not exceed 3 meters.
8、电流表与电流互感器之间的连线必须经过试验端子。
8. The connection between ammeter and current transformer must pass the test terminal.
9、二次线不得从母线相间穿过。
The 9 and two lines must not pass through the busbar.
10、带电阻的ProfibusBus 插头的连接(适用于一根电缆的连接),仅一根电缆连接时,则导线与第一个接口连接。
10, the connection of ProfibusBus plug with resistance (suitable for connection of one cable). When only one cable is connected, the wire is connected with the first interface.
推动开关置“ON”位置
Push the switch to "ON" position
编织的屏蔽带准确的放置在金属导向装置上
The shielded tape is accurately placed on the metal guiding device.
11、带电阻的ProfibusBus 插头的连接(适用于二根电缆的连接)
11. Connection of ProfibusBus plugs with resistance (suitable for connection of two cables)
连接的两根导线是在插头之内的串联。
The two wires connected are connected in series.
推动开关置“OFF”位置
Push the switch to "OFF" position
编织的屏蔽带准确的放置在金属导向装置上
The shielded tape is accurately placed on the metal guiding device.
12、不带电阻的ProfibusBus插头的连接
12, the connection of the ProfibusBus plug without resistance
编织的屏蔽带准确的平放在金属导向装置上。导向装置中的两根红绿线放置在刀口式端子上。
The shielding tape is accurately laid on the metal guiding device. Two red and green lines in the guide device are placed on the knife edge terminals.
绿导线:连接点A
Green wire: connection point A
红导线:连接点B
Red wire: connection point B
13、回拉式弹簧端子的联接
13, the connection of the spring terminal of the back pull type
导线的剥线长度:10㎜
Strip length of wire: 10
导线插入端子口中,直到感觉到导线已插到底部。
The wire is inserted into the terminal port until the wire is inserted into the bottom.
14、抽屉中 Profibus 屏蔽电缆的连接。
14. The connection of the Profibus shielded cable in the drawer.
15、拧紧屏蔽线至约15㎜长为上;
15, tighten the shield line to about 15.
16、用线鼻子把导线与屏蔽压在一起;
16. The wire and the shield are pressed together with the thread nose;
17、压过的线回折在绝缘导线外层上;
17, the pressed wire is folded back on the outer layer of the insulated wire.
用热缩管固定导线连接的部分。
A part of a wire connected by a heat shrinkable tube.
一次回路布线
Primary loop wiring
1、一次配线应尽量选用矩形铜母线,当用矩形母线难以加工时或电流小于
1, a rectangular copper busbar should be selected as far as possible when the wiring is used. When the rectangular busbar is difficult to process, the current will be smaller.